Essential specifications

  • 12-Digit UPC - 785901433217

  • Amperage - 1200 Amp

  • Catalog Number - P1200AWK

  • Circuit Breaker Type - MGL,MJL,PGL,PJL,PKL,PLL

  • Country of Origin - Mexico

Packaging

  • 1 ea

EAN

00785901433217

Part #

143190

Catalog #

P1200AWK

Commercial reference

P1200AWK

12-Digit UPC:

785901433217

Amperage:

1200 Amp

Catalog Number:

P1200AWK

Circuit Breaker Type:

MGL,MJL,PGL,PJL,PKL,PLL

Country of Origin:

Mexico

Current:

1200 Amp

Depths:

241.3 mm

ERP_productname:

SQD P1200AWK TYPE 12 ENCLOSURE FOR PG, PJ CIRCUIT BREAKER

Enclosure:

STEEL

Enclosure Material:

Steel

Family Brand Name:

Square D

Heights:

1346.2 mm

Length:

241.3 mm

Number of Poles:

3P,2 Pole

Sub Brand:

SQUARE D

Type:

MGL-MJL-PGL-PJL-PKL-PLL

Widths:

527.05 mm

SoneparProductId:

SKU_US_26581627

Industrial and residential Square D circuit breaker enclosures designed to be tough, reliable and provide exceptional performance in the most grueling conditions. The enclosure is suitable for service entrance equipment with neutral assembly AL800SN installed. Provides a dead front housing for Power Pact P circuit breakers, molded case switches, and motor circuit protectors to prevent personnel from accidentally contacting energized parts. Encloser acceptes 80 % rated 2 or 3 poles 250A to 1200A circuit breakers. The short circuit current rating of the enclosed circuit breakers is equal to the rating of the circuit breaker installed unless otherwise noted. This NEMA 12/3R without knockouts enclosure has dimensions as Height of 53 inch, Width of 20-3/4 inch and Depth of 9-1/2 inch. Provides NEC 100 compliant sealable equipment. Meet the lock out/tag out requirements of OSHA 29 CFR 1910.147 subpart S. Designed to meet or exceed UL 50 requirements for specific environmental conditions. Complies with NEC 240.30. cULus listed. Protect breaker from physical damage. Allow breaker operation without removing cover Prop 65: WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov - Compatible Products: PJA36120U41A; PKOGTA4; SN1200; PJA36120U44A; S33576MK; PGA36100